Custom Air EquipmentAn HSM Company

COMPARISONCasing and Construction

Roof Curb vs Steel Dunnage vs Piers for Outdoor AHUs

4 min read · Reviewed by the Custom Air Equipment applications team

A roof curb gives an outdoor AHU continuous support and lets ducts drop straight through the roof inside a single flashed enclosure; steel dunnage raises the unit on a structural frame above the roof, keeping the roofing clear and loads on columns; piers or posts are the lightest-touch option for spreading load to specific structure. Choose based on how ducts and piping reach the building, what the roof structure can take, and how the roof will be maintained.

The three support methods

Roof curb

A continuous perimeter frame, usually insulated sheet metal or structural steel, set on the roof deck or structure and flashed into the roofing. The unit sits on top with its base rails bearing on the curb all the way around. Supply and return ducts pass down through the opening inside the curb, so there is one roof penetration for all air connections.

Steel dunnage

Structural steel beams spanning between building columns or major beams, raised above the roof on posts. The unit sits on the dunnage frame, with its base designed for support at the dunnage beams. Ducts and pipes come out of the unit and turn down through separate roof penetrations, often with their own curbs.

Piers or posts

Individual pipe or tube posts with flashed caps, sometimes called equipment supports or stands, carrying short beams or the unit base directly at discrete points. Lighter than full dunnage, used where structure is available at the post locations.

Comparison table

FactorRoof curbSteel dunnagePiers or posts
Load pathDistributed along the curb to the deck and framingConcentrated at columns or major beamsConcentrated at each post
Unit base requirementContinuous bearing; standard base often adequateBase designed to span between dunnage beamsBase designed for point support
Duct connectionsStraight down inside the curb; one penetrationTurned down through separate roof penetrationsAs for dunnage
Roof penetrationsOne large openingSeveral smaller ones, plus postsPosts plus duct and pipe penetrations
FlashingPerimeter flashing of the curbEach post and each duct curb flashedEach post flashed
Roof replacementMust work around the curb; unit staysRoofers can work under the unitRoofers can work under, between posts
Clearance under unitNoneTypically enough to reach the roof surfaceDepends on post height
Condensate trap heightMust fit within base and curb height or inside the curbAmple height below the unitUsually ample
Vibration isolationIsolation curbs availableIsolators between unit and dunnageIsolators at posts
Seismic and wind anchorageUnit anchored to curb, curb anchored to structureUnit anchored to steel; steel to columnsUnit anchored to posts
Typical cost driversCurb fabrication, structural framing at openingStructural steel, post flashings, duct curbsPosts, flashings, base reinforcement
AcousticsDucts and casing directly over the space below; breakout concernAir gap between unit and roof helpsSimilar to dunnage

When a curb makes sense

  • Ducts can drop straight down into the building below the unit.
  • The roof structure can carry the distributed load, or framing around the curb opening can be designed to do so.
  • The unit is a replacement for an existing curb-mounted unit and an adapter curb can be used.
  • The owner wants the fewest roof penetrations.

Watch the curb height: it must provide the snow clearance required in the region and enough height for condensate traps on the coil and humidifier sections. Acoustic treatment inside the curb can reduce noise into the space below; see rooftop breakout noise.

When dunnage or piers make sense

  • The roof deck cannot carry the unit, but columns or major beams can.
  • Duct connections must leave the unit through the side or end and travel some distance before entering the building.
  • The roof membrane will need replacement during the unit's life, and the owner wants roofers to have access under the equipment.
  • Heavy snow regions where the unit must sit well above drifts.
  • Large, heavy units where a curb would require extensive deck reinforcement.

The AHU base must be designed for point support at the dunnage or post locations. Give the manufacturer the support layout early; see AHU base frames.

Coordination checklist

  1. Structural engineer confirms load path and supports for operating, seismic, wind and snow loads.
  2. Roofing designer details curb or post flashings compatible with the roof system and its warranty.
  3. Mechanical engineer confirms duct and pipe routes and the number of penetrations.
  4. AHU manufacturer receives support type and locations, and confirms base design and anchor points.
  5. Trap heights for condensate drains are checked against curb or dunnage height.
  6. Access around and under the unit for service and roof maintenance is confirmed.

For the installation sequence itself, including setting the unit on a curb and sealing, see roof curb installation. If you are weighing support options for a new rooftop unit, sharing the roof framing plan and duct routes through the contact page lets the base be designed for the support you choose.

Common questions

Is a roof curb or steel dunnage better for a rooftop AHU?

A roof curb suits units whose ducts drop straight down and whose roof can carry distributed load, with one roof penetration. Dunnage suits heavy units, side duct connections, weak decks and roofs that will need replacement under the unit.

Can an air handler sit on steel dunnage?

Yes, if its base is designed to span between the dunnage beams. The manufacturer needs the support locations to size the base and locate anchor points.

How high should a roof curb be?

High enough to meet local snow clearance and roofing requirements and to fit the condensate traps for the unit's drain pans. Curb heights vary by region and unit; coordinate with the roofing designer and the unit manufacturer.

Ready to build the unit your project actually needs?