Custom Air EquipmentAn HSM Company

EXPLAINERAcoustics and Vibration

Reading AHU Octave Band Sound Data

4 min read · Reviewed by the Custom Air Equipment applications team

AHU sound data is a table of sound power levels split into octave bands, usually 63 Hz to 8,000 Hz, with separate rows for the inlet, discharge and casing-radiated paths. Read it band by band and path by path; a single overall number hides almost everything an acoustician needs.

What an octave band is

An octave is a frequency range whose upper limit is twice its lower limit. HVAC data uses the standard octave bands named by their centre frequencies:

BandCentre frequencyApproximate rangeTypical HVAC sources
163 Hz44 to 88 HzFan rumble, turbulence, low-speed blade pass of large wheels
2125 Hz88 to 177 HzFan broadband noise, duct rumble
3250 Hz177 to 355 HzFan noise, blade pass of many plenum fans
4500 Hz355 to 710 HzFan and air noise, damper noise
51,000 Hz710 to 1,420 HzSmall-fan blade pass, air turbulence at fittings
62,000 Hz1,420 to 2,840 HzRegenerated noise, high-velocity hiss
74,000 Hz2,840 to 5,680 HzHiss at grilles and dampers, motor and drive whine
88,000 Hz5,680 to 11,360 HzDrive switching noise, very high-velocity air

Some reports add a 31.5 Hz band. It is rarely tested accurately in standard reverberant rooms, so treat values there with caution and confirm whether they were measured or extrapolated.

Why the low bands matter most

Duct lining, silencers and ceiling plenums attenuate high frequencies efficiently and low frequencies poorly. A table can show a high 2 kHz value that will vanish by the time air reaches the room, while a 63 Hz value only a few decibels lower will pass almost untouched through the ductwork and casing. When comparing two selections, look first at 63, 125 and 250 Hz. Those bands drive most complaints about rumble, and they also drive the cost of attenuation, because low-frequency silencers are long and pressure-hungry.

A unit that is "5 dB quieter overall" can be louder where it counts. Always compare bands, not totals.

The three data sets: inlet, discharge and casing-radiated

A complete data sheet lists sound power for each opening or surface through which sound leaves the unit:

  • Discharge (supply outlet): sound power travelling down the supply duct toward the occupied spaces. Usually the largest number and the one most often attenuated with silencers.
  • Inlet (return or outdoor-air opening): sound travelling back upstream through the return duct or out of the outdoor intake. Return paths are often short and lightly attenuated, so inlet data frequently governs.
  • Casing-radiated: sound passing through the unit's panels into the mechanical room or to the outdoors. It depends on casing construction and is reported as the total power radiated by the casing surface.

Some manufacturers also report "fan-only" sound power at the wheel. That is not the same as unit discharge data, because coils, filters, plenums and lined sections between the fan and the opening absorb some energy and the casing changes how it radiates. Ask which one you are looking at. How each set reaches an occupant is explained in inlet, discharge and casing-radiated sound paths.

A-weighting and what it hides

Human hearing is less sensitive at low frequencies. A-weighting applies a correction to each band to approximate that response, then sums the result into one dBA value. The standard A-weighting corrections at octave-band centres are:

631252505001k2k4k8k
−26.2−16.1−8.6−3.20+1.2+1.0−1.1

The 63 Hz correction subtracts 26 dB before summing. That is why a fan with a strong rumble can still show a modest dBA. A-weighted sound power (dBA Lw) is useful for quick ranking of similar equipment and for outdoor noise screening, but it should never replace octave-band data in a design calculation. For how weighting relates to room criteria, see NC vs RC vs dBA.

Reading a data sheet line by line

Take this example discharge row for a single plenum fan selection:

Path631252505001k2k4k8kLwA
Discharge949291888581777291
Inlet929088848076726787
Casing868072645852474268

What to notice:

  1. The spectrum slopes downward at roughly 2 to 4 dB per octave on the airside paths, which is typical of broadband fan noise. A band that sticks up above that slope usually indicates a tone, often blade pass; see fan blade pass frequency and tonal noise.
  2. The casing row falls steeply because panels block high frequencies much better than low ones. At 63 Hz the casing is only 8 dB below the discharge, so in a lightweight mechanical room casing noise can still matter.
  3. The A-weighted totals are dominated by 250 Hz through 1 kHz, even though 63 Hz is the highest unweighted band.

Questions to ask before using the numbers

  • Is the data at the scheduled airflow and static pressure, or at a catalogue rating point?
  • Was it tested, or calculated from fan-only data with corrections? If tested, to which standard (for example AHRI 260 for ducted units, AMCA 300 for fans)?
  • Does it include the effect of the actual unit sections, such as silencers, lined plenums or coils between fan and opening?
  • For fan arrays, is it the combined level of all running fans at the operating speed?
  • Is 63 Hz data measured, or omitted because the test room could not qualify it?

Getting clear answers to these questions before a design review saves rework later, when an acoustician pushes the data through the duct and room path.

Common questions

What does 63 Hz mean on an AHU sound data sheet?

It is the octave band centred on 63 Hz, covering roughly 44 to 88 Hz. It captures low-frequency rumble, which is hard to attenuate and passes easily through ducts and walls. It is often the band that decides whether a space meets its criterion.

Why are inlet and discharge sound levels different?

The fan radiates different energy upstream and downstream, and the sections between the fan and each opening absorb different amounts. Coils, filters and lined plenums on the inlet side can reduce inlet levels, while a short discharge plenum may add little attenuation.

Can I use dBA sound power to compare two air handlers?

Only as a rough first screen of similar units. A-weighting suppresses low frequencies by up to 26 dB, so two units with the same dBA can have very different low-frequency content. Use octave-band data for any decision.