HOW-TOHumidification and Dehumidification
How to Achieve Supply Dew Points Below 40 F
Below about 40 F dew point, ordinary chilled water coils run out of reach. Get there by staging: a conventional coil removes the bulk of the moisture, a low-temperature coil or a desiccant wheel takes the air the rest of the way, and frost on any coil surface below 32 F is managed by defrost or by handing the job to the desiccant. Choose the split based on the target dew point, the energy available for regeneration, and how many hours a year the system runs.
Step 1: Confirm the target and the load
- State the required supply dew point and the tolerance, for example 35 F ± 2 F.
- Calculate the supply airflow and the moisture to be removed from the design entering condition down to the target. Use the latent load method in calculating latent load and required supply dew point.
- Check whether the space truly needs that dew point continuously, or whether a slightly higher value would meet the requirement for most hours.
- Identify the dehumidification design day for the site, which is usually a humid day rather than the hottest one.
Step 2: Understand what each method can reach
| Method | Practical supply dew point floor | Notes |
|---|---|---|
| Chilled water coil, 42 to 45 F water | Mid to high 40s F | Limited by water temperature and coil approach |
| Low-temperature chilled water or glycol, 34 to 38 F | About 40 F | Needs a dedicated low-temperature plant or heat exchanger |
| DX coil at low suction temperature | About 35 to 40 F | Coil surface below 32 F; frost risk |
| Brine or glycol below freezing with defrost | Low 30s F and below | Requires defrost cycles or parallel coils |
| Desiccant wheel | Well below 32 F | Requires reactivation heat; process air leaves warm |
| Coil plus desiccant | Well below 32 F with smaller wheel | Most common for very low dew points |
The desiccant mechanism, including reactivation energy, is covered in desiccant dehumidification wheels and regeneration.
Step 3: Precondition with a conventional coil
- Place a chilled water or DX coil first in the process airstream to bring outdoor air down to a dew point in the high 40s to low 50s F.
- This stage removes most of the moisture at the lowest cost per pound, since it uses ordinary chilled water.
- Size it at the design humid day, with face velocity and fins chosen to avoid carryover, and provide a drain pan suited to heavy condensate.
- If energy recovery is available from exhaust, place it ahead of this coil to reduce its load.
Step 4: Finish with a low-temperature coil or a desiccant
Option A: second, colder coil
- Add a second coil fed by low-temperature chilled water, glycol or DX at low suction.
- For dew points near 40 F, coil surfaces may stay above freezing; check fin temperature at the leaving air side.
- For targets below about 38 F, plan for frost on the coil surface.
Option B: desiccant wheel after the precooling coil
- Feed precooled, near-saturated air into the desiccant wheel. Cool, moist entering air lets the wheel reach lower dew points with less reactivation energy than warm air would.
- Select reactivation temperature and wheel face area for the target dew point at design entering conditions.
- Add a post-cooling coil after the wheel to remove the heat of adsorption and carryover, bringing the supply to the required dry-bulb.
- Choose a reactivation heat source: gas, steam, hot water or recovered heat. Cheap or recovered heat makes this option much more attractive.
Post-cooling after a desiccant wheel is sensible only, because the air is already dry. It can use warmer chilled water or even cooling tower water in some climates, which helps the energy balance.
Step 5: Manage frost
Any coil whose surface runs below 32 F will collect frost from the air's moisture, raising pressure drop and eventually blocking airflow.
- Use parallel coils that alternate: one dehumidifies while the other defrosts with warm fluid, hot gas or air.
- Alternatively, schedule timed defrost cycles if the process can tolerate a brief rise in supply dew point, which is rare for critical applications.
- Monitor coil air pressure drop to trigger defrost based on actual frost rather than time alone.
- Where frost management becomes complex, shift more of the work to a desiccant wheel so coil surfaces can stay above freezing.
Do not specify a DX coil to deliver a dew point in the low 30s F without a defrost strategy. It will work on startup and fail within hours as the coil frosts over.
Step 6: Control the system
- Control to supply dew point measured by a sensor suited to low humidity, such as a chilled mirror or a polymer sensor rated for low dew points.
- Stage the precooling coil to a fixed leaving dew point, typically the minimum it can reliably reach.
- Modulate the second stage, either the low-temperature coil or the wheel's reactivation heat, to hold the final dew point.
- Control post-cooling to the supply dry-bulb setpoint.
- Alarm on high supply dew point, reactivation airflow failure and coil frost pressure drop.
Step 7: Detail the air handler
- Build the casing for very low dew point air: tight construction and well-sealed panels, since moist ambient air leaking in raises the supply dew point.
- Check for condensation on the casing exterior where cold, dry supply air runs through a warm, humid mechanical room; insulate and thermally break as needed.
- Provide separate reactivation intake and exhaust paths if a desiccant is used, with exhaust located away from intakes.
- Plan for duct leakage: dry air ducts passing through humid spaces pick up moisture through leaks, raising the delivered dew point.
Battery dry rooms and similar extreme applications are covered separately; see battery dry room air handling.
Common questions
How do you get supply air dew point below 40 F?
Use a conventional coil to remove most of the moisture, then finish with a low-temperature coil or a desiccant wheel. Coils below freezing need defrost; desiccants need reactivation heat and post-cooling.
Can a chilled water coil reach a 40 F dew point?
Not with standard 42 to 45 F chilled water. It typically needs low-temperature chilled water or glycol in the mid 30s F, and colder still for lower dew points.
Why precool air before a desiccant wheel?
Cool, nearly saturated air entering the wheel lets it reach a lower dew point with less reactivation energy. The precooling coil removes the bulk of the moisture cheaply with ordinary chilled water.